CRIR M1(C06-0801-000) Honeywell CO2 Sensor
$12.6
$21.92
For Bulk requirement, Kindly click on enquiry now button Product Details: Product Description Brand Honeywell Model no. C06-0801-000 CO2 Target gas carbon dioxide (CO2) Operating principle non-dispersive infrared (NDIR) Standard range1, 2 400 ppm to 2000 ppm, up to 10000 ppm extended range Measurement interval 4 s Accuracy 3 ±40 ppm ±3% of reading Typical response time (T90) <120 s Sensor warm-up time 3 min typical Repeatability >97% Operating voltage 4.5 V to 5.5 V unprotected against surges and reverse connection Power consumption 300 mA peak, 30 mA average Alarm output, open collector 1000 ppm/800 ppm normal state is conducting max 100 mA. Transistor open at CO2 high or at sensor failure (see Figure 1). Serial communication5 UART, Modbus protocol Operating temperature range 0°C to 50°C Storage temperature range -40°C to 70°C Operating humidity 0 %RH to 90 %RH non-condensed Expected operating life 10 years Maintenance6 maintenance-free for normal indoor applications Weight <8 g Dimensions 33 mm x 22 mm X 11,2 mm (tolerance ±0,5 mm) Above specifications mentioned are for quick reference only. Actual technical details has to be obtained from below catalog.